Viessmann · Boiler troubleshooting
Check the return temperature sensor
What is going on
Use this to check a strap-on or immersion return temperature sensor against the actual temperature.
Check in this order
- Disconnect the sensor from the terminals.
- Measure the sensor resistance between terminals 1 and 2 of the plug.
- Compare the reading with the resistance table for the current return temperature.
- If the value differs significantly, check the installation and replace the sensor if needed.
Applies to: Return temperature sensor, strap-on or immersion
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100/300-K installation and service instructions, p. 63. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.