Wire thermostats and dry contact inputs
What is going on
Inputs are dry contacts only. The boiler does not supply 24V to thermostat circuits.
Check in this order
- Do not supply 24 VAC to the thermostat or input circuits.
- If a thermostat needs continuous 24V power, connect its common wire (C). Keep total draw at or below 120 mA at 24VAC per thermostat.
- For 3-wire zone valves, use relays to give the control dry contacts (the valve end switch carries 24VAC).
- Connect each thermostat or aquastat to its matching input terminal.
Applies to: ECO Tec Series 3 all models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.