Connecting several remote control units
What is going on
Several remote controls and additional KM BUS users are connected through a junction box installed on site. Version 1 is for remote controls only; version 2 also adds other KM BUS users.
Check in this order
- Install a junction box on site.
- Connect the control unit, Vitotrol 1, 2 and 3 through the junction box as shown in the connection diagram.
- For version 2, connect additional BUS users through the same junction box.
- Keep the total length of all KM BUS cables to 50 m / 164 ft.
- Keep each remote control branch to a maximum of 15 m.
Applies to: Multiple Vitotrol remote controls on KM BUS
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 200-H installation and service instructions, p. 47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.