Connecting several remote control units

Vitotronic 200-H

What is going on

Several remote controls and additional KM BUS users are connected through a junction box installed on site. Version 1 is for remote controls only; version 2 also adds other KM BUS users.

Check in this order

  1. Install a junction box on site.
  2. Connect the control unit, Vitotrol 1, 2 and 3 through the junction box as shown in the connection diagram.
  3. For version 2, connect additional BUS users through the same junction box.
  4. Keep the total length of all KM BUS cables to 50 m / 164 ft.
  5. Keep each remote control branch to a maximum of 15 m.

Applies to: Multiple Vitotrol remote controls on KM BUS

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200-H installation and service instructions, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.