Navien · Boiler troubleshooting

Lost or incorrect gateway IP address

Modbus/BACnet Gateway

What is going on

Find the gateway on the network with the FieldServer Toolbox and correct its IP.

Likely causes

  • IP address unknown or changed

Check in this order

  1. Make sure FieldServer Toolbox is installed on the local PC; download it from the Sierra Monitor website if not.
  2. Connect a standard Cat-5 cable between the PC and the gateway Ethernet port.
  3. Open FS Toolbox Utility and click Discover Now.
  4. Note the gateway's IP address.
  5. To change it, click the settings icon on the gateway row, choose Network Settings, change the IP, and click Update IP Settings.

Applies to: Gateway Ethernet access

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Modbus/BACnet Gateway Start-up Guide, p. 18. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.