Viessmann · Boiler troubleshooting

Boiler piped into a heating/cooling system with chiller

Vitodens 200-W B2HB

What is going on

When the boiler is used with a chiller, the chilled water must be piped in parallel with the boiler using valves, so chilled water cannot enter the boiler. Heating coils in air handlers that see refrigerated air need flow control valves or equivalent to stop gravity circulation during cooling. Follow the chiller maker's installation requirements as well.

Likely causes

  • Chilled medium entering the boiler
  • Gravity circulation through the boiler during the cooling cycle

Check in this order

  1. Pipe the chilled medium in parallel with the boiler.
  2. Fit valves so chilled medium cannot enter the boiler.
  3. Fit flow control valves on heating coils in air handlers that may see refrigerated air.
  4. Label the changeover valves v1 and v2.
  5. Run the circulating pump from its own on/off switch, not from the boiler pump aquastat.
  6. When cooling season starts, close v1 and open v2.
  7. When heating season starts, close v2 and open v1.

Applies to: Vitodens 200-W B2HB boiler connected to a water chiller (heating/cooling application)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 43. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.