Weil-McLain · Boiler troubleshooting
Expansion tank connection (closed-type tank)
What is going on
Connection details for a closed-type expansion tank. An undersized tank causes water loss at the relief valve and makeup water at the fill valve, which can lead to section failure.
Likely causes
- Undersized expansion tank.
- Tank connected at the wrong point.
Check in this order
- Size the tank for the boiler and system water volume and temperature.
- Connect the tank to the 1/2 in. NPT tapping behind the supply outlet using 1/2 in. NPT piping.
- Pitch horizontal piping up toward the tank at 1 in. per 5 ft.
- Connect the fill line only at the expansion tank, never at another point in the system.
Applies to: Closed-type expansion tank, Figure 16
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG/PEG Series 7 boiler manual, p. 21. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.