Weil-McLain · Boiler troubleshooting

Expansion tank connection (closed-type tank)

EG / PEG Series 7

What is going on

Connection details for a closed-type expansion tank. An undersized tank causes water loss at the relief valve and makeup water at the fill valve, which can lead to section failure.

Likely causes

  • Undersized expansion tank.
  • Tank connected at the wrong point.

Check in this order

  1. Size the tank for the boiler and system water volume and temperature.
  2. Connect the tank to the 1/2 in. NPT tapping behind the supply outlet using 1/2 in. NPT piping.
  3. Pitch horizontal piping up toward the tank at 1 in. per 5 ft.
  4. Connect the fill line only at the expansion tank, never at another point in the system.

Applies to: Closed-type expansion tank, Figure 16

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG/PEG Series 7 boiler manual, p. 21. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.