Viessmann · Boiler troubleshooting

LON participant check

Vitotronic 300-KVitotronic 200-H

What is going on

The participant check tests communication between the fault manager and the devices on the LON system. The control must be the fault manager (code 79:1) and the participant list must be current.

Check in this order

  1. Confirm the control is set as fault manager (code 79:1).
  2. Confirm each control has its LON participant number set.
  3. Press OK and the service button together for about 4 seconds.
  4. Select Service functions, then Participant check.
  5. Select the participant to test (e.g. participant 12).
  6. Read the result OK means passed, Not OK means failed.
  7. To run a new check, create a new participant list with Delete list?.

Applies to: Vitotronic 300-K and 200-H on LON

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 and 300-K Installation and Service Instructions, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.