Install and check the return temperature sensor
What is going on
Strap-on or immersion sensor that measures boiler return temperature. Plugs into socket 17A or 17B.
Check in this order
- Disconnect plug aJA or aJB in the boiler control terminal compartment.
- Measure resistance at terminals 1 and 2 of the plug.
- Compare the reading with the return temperature using the resistance table.
- If the value differs significantly, check installation and replace the sensor if needed.
- Plug the sensor into socket 17A or 17B.
Applies to: Return temperature sensor, sockets 17A/17B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 300 Installation and Service Instructions, p. 28. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.