Viessmann · Boiler troubleshooting

Check heating water side connections for leaks

Vitocrossal 200 CI2

What is going on

Check all heating water connections, including control equipment and the minimum pressure monitor (low-water cutoff). Open heating water connections only when the boiler is unpressurized. Under-pressure can damage the boiler, so empty it through open venting with a suction pump.

Check in this order

  1. Confirm the boiler is unpressurized before opening any heating water connection.
  2. Check all heating water connections for leaks.
  3. Check connections for control equipment and the low-water cutoff for leaks.
  4. If emptying the boiler, use a suction pump with open venting.

Applies to: Vitocrossal 200 CI2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 32. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.