Viessmann · Boiler troubleshooting

Clean the DHW storage tank

Vitodens 222-F, B2TB

What is going on

Visual inspection and cleaning must be done no later than two years after commissioning and then as needed. Do not use hydrochloric acid based cleaners. Use only plastic cleaning tools inside the tank.

Likely causes

  • Loose deposits inside the DHW tank
  • Hard deposits that a high pressure cleaner cannot remove

Check in this order

  1. Drain the DHW storage tank.
  2. Remove insulation A.
  3. Disconnect the DHW piping from the pipework to stop contamination entering the system.
  4. Remove the tank clean-out cover B.
  5. Remove loose deposits with a high pressure cleaner.
  6. Use a chemical cleaner for hard deposits. Never use hydrochloric acid based agents.
  7. Flush the DHW tank thoroughly.
  8. Refit in reverse order.

Applies to: DHW storage tank

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 222-F B2TB 19, 35, 68, 125 Service Instructions, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.