Route and seal wiring in the cabinet
What is going on
Line voltage and low voltage use separate knockouts. All entrances must be sealed.
Check in this order
- Route line voltage through the bottom front left knockouts into the high voltage junction box. Strip wire no more than 1/4 in.
- Route low voltage through the bottom right or top right knockouts and connect directly to the matching terminal block.
- Use a strain relief at every knockout.
- Seal all electrical entrances with a sealed strain relief or duct seal putty or silicone to stop the boiler drawing air from the boiler room.
- Bundle wires with the supplied wire ties and secure the tie mount to the control bracket bottom right mounting hole.
- Install an On/Off service switch in a junction box near the boiler if required.
Applies to: ECO Tec Series 3 all models
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec series 3 condensing gas boiler boiler manual, p. 66-67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.