Viessmann · Boiler troubleshooting
Convert fuel type from natural gas to liquid propane gas
What is going on
Coding and gas valve change to run the boiler on LPG. The factory setting is natural gas.
Check in this order
- Set adjusting screw A on the gas valve to "2" using a 2.5 mm hex key.
- Switch the ON/OFF switch "8" to ON. Slide the black control cover outwards to reach it.
- Call up coding level 2 (see page 47).
- Select "General".
- Set coding address 11 to value 9.
- Set coding address 82 to value 1 (liquid propane gas).
- Go back to coding address 11 and select any value except 9.
- Exit coding level 2 and open the gas shut-off valve.
- Apply the supplied fuel conversion labels.
Applies to: Vitodens 200-W B2HA 19, 28, 35
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitodens 200-W B2HA service instructions, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.