Weil-McLain · Boiler troubleshooting

Expansion tank and make-up water piping

SVF

What is going on

Size the expansion tank for the boiler and system water volume and temperature (boiler water content on page 120). An undersized tank lets water blow out of the relief valve and add make-up water through the fill valve, which can eventually fail the boiler. Connect the tank to the air separator only if the separator is on the pump suction side. Install the system fill connection at the same point as the expansion tank connection. With a diaphragm or bladder tank, put an automatic air vent on top of the air separator, and where the boiler sits above main piping, put one in the outgoing boiler piping. Pre-charge diaphragm tanks to the system fill pressure before connecting. With a closed-type tank, do not install automatic air vents, pitch horizontal piping up toward the tank 1 inch per 5 feet, and use at least 3/4 inch piping to the tank.

Likely causes

  • Undersized expansion tank
  • Automatic air vent installed on a closed-type tank
  • Fill point not at the same point as the tank connection

Check in this order

  1. Confirm the tank volume handles boiler and system water volume and temperature (see page 120).
  2. Connect the tank to the air separator only if the separator is on the pump suction side.
  3. Put the system fill connection at the same point as the expansion tank connection.
  4. For a diaphragm tank, pre-charge it to fill pressure and fit an automatic air vent on the air separator.
  5. For a closed-type tank, skip automatic air vents, pitch horizontal piping up 1 inch per 5 feet toward the tank, and use at least 3/4 inch piping.

Applies to: All SVF 1500-3000 system piping

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 16. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.