Weil-McLain · Boiler troubleshooting
Pilot lights but does not energize main gas valve
What is going on
The pilot is lit but the main valve does not come on, usually because the flame signal does not register.
Likely causes
- Flame signal below 60 in control diagnostics
- Pilot flame sense wiring or flame rod faulty
- Low inlet gas pressure with pilot regulator in use
Check in this order
- Check the Pilot Flame Signal in control diagnostics. A signal below 60 is not proven flame.
- If the signal does not register, check the Pilot Flame Sense wiring and the flame rod for continuity and corrosion. Replace the rod if necessary.
- If a pilot gas pressure regulator is used with low inlet pressure, increase the pilot regulator setting to supply more gas to the pilot.
Applies to: EG water boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: EG / PEG Series 7 Boiler Manual, p. 75. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.