Weil-McLain · Boiler troubleshooting

Pilot lights but does not energize main gas valve

EG / PEG Series 7

What is going on

The pilot is lit but the main valve does not come on, usually because the flame signal does not register.

Likely causes

  • Flame signal below 60 in control diagnostics
  • Pilot flame sense wiring or flame rod faulty
  • Low inlet gas pressure with pilot regulator in use

Check in this order

  1. Check the Pilot Flame Signal in control diagnostics. A signal below 60 is not proven flame.
  2. If the signal does not register, check the Pilot Flame Sense wiring and the flame rod for continuity and corrosion. Replace the rod if necessary.
  3. If a pilot gas pressure regulator is used with low inlet pressure, increase the pilot regulator setting to supply more gas to the pilot.

Applies to: EG water boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: EG / PEG Series 7 Boiler Manual, p. 75. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.