External blocking via output contact (EA1 extension)

Vitocrossal 300 CA3B Dual Fuel

What is going on

A potential-free contact can block the boiler. When it closes, the burner of each boiler section shuts down, the boiler circuit pump and system pump switch off, and shut-off devices close. The heating system has no frost protection during the block.

Check in this order

  1. Wire a potential-free dry contact to the EA1 extension. Do not apply voltage to it.
  2. Set coding 5D (DE1), 5E (DE2) or 5F (DE3) in the General group to 3 or 4, depending on the input used.
  3. Note that the heating system has no frost protection while the block is active.

Applies to: External blocking input on EA1 extension

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 installation instructions, p. 33. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.