Viessmann · Boiler troubleshooting

Flue gas and supply temperature sensors (self-check)

Vitocrossal 200 CI2

What is going on

Both flue gas and supply temperature sensors are double sensors. The control compares the two readings continuously, so a manual check is not needed. A faulty sensor locks the boiler out.

Likely causes

  • Sensor readings disagree, so plausibility check fails

Check in this order

  1. Read the fault code F.694 for the flue gas sensor, F.446 for the supply sensor.
  2. Replace the faulty sensor.
  3. Unlock the boiler at the programming unit.

Applies to: Vitocrossal 200 CI2

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 Service Instructions, p. 77. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.