Check expansion tank
What is going on
Confirm the tank is the correct type, size and charge.
Likely causes
- Closed-type tank waterlogged: the relief valve weeps often.
- Diaphragm or bladder tank too small or membrane damaged: the relief valve weeps often.
Check in this order
- Check the tank type and location. Open-type tanks sit above the highest radiator or baseboard. Closed-type tanks are welded, sit above the boiler, and are partly filled with water.
- Closed-type tanks need a tank fitting such as the B and G Tank-Trol or Taco Taco-Trol. Do not use automatic air vents on systems with closed-type tanks.
- Diaphragm or bladder tanks need at least one automatic air vent, preferably on top of an air eliminator.
- If the relief valve weeps often, check the tank. For a closed-type tank, check fill level per the fitting maker's instructions, then check tank size and replace with a larger tank if needed.
- For a diaphragm or bladder tank, check that it is large enough. Add tanks if needed. If size is correct, remove it and check charge pressure (usually 12 psig for residential). Replace the tank if it will not hold pressure.
Applies to: SlimFit 550 and 750 Series 3
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit series3 commercial gas-fired water boiler boiler manual, p. 93. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.