Weil-McLain · Boiler troubleshooting

Replace the flue pressure switch

SVF 500/600 Series 1

What is going on

Replacement procedure for the flue pressure switch.

Check in this order

  1. Disconnect the tube on the tap of the flue pressure switch.
  2. Disconnect the two wires running to the switch.
  3. Remove the two screws holding the switch to the vertical support.
  4. Install the new switch with two new screws.
  5. Reconnect the two wires and the tube, then recheck operation.

Applies to: SVF 500/600 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain SVF 500/600 boiler manual, p. 114. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.