Viessmann · Boiler troubleshooting
Connecting the external 0-10 V signal
What is going on
Wiring an external 0-10 V demand signal that sets the maximum boiler water temperature.
Check in this order
- Connect the external 0-10 V signal to the 0-10V plug on extension module EA1.
- Check polarity.
- Use the manufacturer's chart to find the maximum boiler water temperature for the signal voltage.
- Example from the manual 8 VDC equals 176 ºF (80 ºC).
Applies to: Models 45, 60
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 45, 60 Installation Instructions, p. 50. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.