CSD-1 fixed high limit test, simulation #1 (boiler pump off)
What is going on
Field test of the fixed high limit using the flue gas test mode with the boiler pump disconnected. Only do this where required by law and accept that the test can overheat the system.
Check in this order
- Make sure the boiler and boiler pump are in normal operating condition.
- Remove the cover at the back of the boiler control to reach the control plugs.
- In the extended menu, select Test mode, then flue gas test ON, and press OK.
- Wait for the burner to ignite and go to high fire.
- Once the burner ignites, unplug the boiler pump plug from the boiler control board, gently with pliers.
- Watch the boiler temperature on the display. The burner shuts off as temperature rises.
- Confirm the boiler temperature keeps rising until the high limit trips at 210°F (99°C) and shows F2.
- If the limit is not reached, two minutes after the burner shuts off, briefly energize the boiler pump for no more than 1 second by plugging the pump plug back in, then repeat the test.
Applies to: Vitodens 200-W B2HA boilers, where required by law
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA installation manual, p. 7. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.