Boiler room combustion air openings

SlimFit Series 3

What is going on

Direct exhaust boilers take combustion and ventilation air from the boiler room. Openings must be sized for all appliances and air movers in the room. If the room is tight construction, provide outside air openings. Openings must not be under negative pressure from exhaust fans. Free area is after louver or grille reduction. Use the sizing rules in the manual.

Likely causes

  • Negative pressure from exhaust fans or other ventilation devices
  • Louvers or grilles reducing free area
  • Tight building construction

Check in this order

  1. Calculate total appliance input in Btuh for the room.
  2. Size openings using the manual's rule for the number of appliances in the room (two openings or a single opening).
  3. Subtract louver or grille blockage from the free area.
  4. Check that the room is not under negative pressure.
  5. For a single opening, make sure it opens directly to outdoors, its top is within 12 in of the ceiling, and its free area is at least the sum of all vent connector areas in the space.

Applies to: Direct exhaust installations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit series 3 commercial gas-fired water boiler manual, p. 26. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.