Install modulating valve adaptor and actuator

Vitocontrol-S VD2/CT3/CM2Vitotronic 100

What is going on

Use the 120V or 24V valve adaptor matching the actuator.

Check in this order

  1. Disconnect power to the control.
  2. Mount the 120V or 24V valve adaptor on the DIN rail inside the connection enclosure.
  3. Insert the adaptor plug into socket gS on the control.
  4. Fasten the cable with a tie.
  5. Connect the black adaptor wire to terminal 8, 9 or 10 on the DIN rail.
  6. Connect the valve actuator wires to the adaptor terminals as shown in the figures.

Applies to: Modulating valve actuators

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Viessmann Vitocontrol-S VD2/CT3/CM2 installation manual, p. 83. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.