Viessmann · Boiler troubleshooting
Replace air pressure switch
What is going on
Replace the air pressure switch on the burner control bracket.
Check in this order
- Disconnect the air tube from the air pressure switch.
- Remove the M6 (5 mm hex key) screw and the ground wire from the control bracket. Loosen the second bracket screw and pivot the bracket aside.
- Remove the two cover screws and the cover.
- Remove the two M4 (3 mm hex key) screws and the pressure switch.
- Loosen the two programming unit screws to reach the switch cable connector.
- Cut the cable tie, release the connector locking tab and remove the cable.
- Reinstall the new switch. Tighten the bracket M6 screw to the torque in the torque table.
- Make sure the ground wire is secure. Set the new air pressure settings to match the old switch exactly.
Applies to: APS1 (blower) and APS2 (combustion chamber)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CM2 186 to 311 Service Instructions, p. 34. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.