Weil-McLain · Boiler troubleshooting

Route the relief valve discharge line

SlimFit Series 2

What is going on

Discharge piping must be installed to protect people and property. The piping must follow local or state codes and the manufacturer guidelines.

Check in this order

  1. Connect the discharge line to the relief valve outlet and run it to a safe disposal point.
  2. Keep the discharge line as short as possible and the same size as the valve outlet along its full length.
  3. Pitch the line downward from the valve and end it at least 6 inches above a floor drain where discharge is visible.
  4. End the line plain, not threaded, using material rated for 375 °F or higher.
  5. Do not route the line where freezing can occur, and do not add a shutoff valve or any obstruction in it.
  6. After filling and pressurizing the system, lift the lever to test the valve. Confirm it discharges freely. Replace the valve if it does not operate correctly.

Applies to: SlimFit 1000-2000 Series 2 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit Series 2 Boiler Manual, p. 14. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.