Navien · Boiler troubleshooting

Zone pump wiring for up to four zones

NCB700

What is going on

Wiring notes for running up to four zone pumps from the boiler. Each zone output is rated for a maximum of 2.5 A.

Check in this order

  1. Use dry-contact zone pump connections when the thermostats are not powered by 24 VAC.
  2. Use the 24 VAC thermostat inputs when the thermostats supply their own 24 VAC.
  3. Connect each zone pump to its line and neutral. Keep each pump at or below 2.5 A.
  4. Connect the zone 4 pump wire to the recirculation pump connection, if zone 4 is used.
  5. Connect the system pump on the air handler setup to the boiler pump terminals, at 2.5 A maximum, with ground.

Applies to: NCB700 multi-zone wiring

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Navien NCB700 installation and operation manual, p. 57-61. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.