Viessmann · Boiler troubleshooting
Check the ignition and ionization electrodes
What is going on
Check that the electrodes are undamaged and at the correct distance from the burner tube.
Likely causes
- Damaged electrodes
- Incorrect electrode distance from burner tube
Check in this order
- Check the electrode block once the burner plate is removed.
- Check the ignition electrodes and the ionization electrode for damage and correct distance from the burner tube.
- Replace any electrode that is damaged or out of position.
- Refit the electrode block with new gaskets (4.4 lb.ft / 6 Nm).
Applies to: Vitocrossal 300 CA3B Dual Fuel 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Dual Fuel Series 2.5 to 6.0 service instructions, p. 72. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.