System layout 1: DHW tank, mixing valve and radiator loops
What is going on
Layout 1 uses one boiler with a DHW storage tank, one heating circuit without a mixing valve, and two heating circuits with a mixing valve: a high-temperature radiator loop and a low-temperature underfloor loop. The 3-way mixing valve is controlled by an accessory kit. Underfloor systems with non-oxygen diffusion barrier tubing need system separation, and all components on the secondary side must be corrosion-resistant. A hydronic pressure bypass may be required with single-speed pumps. All pumps are field supplied.
Check in this order
- Install the boiler supply and return with the mixing valve and its temperature sensor.
- Connect the outdoor sensor, DHW tank sensor and system supply sensor as shown in the layout.
- Fit a hydronic pressure bypass if single-speed boiler or system pumps are used.
- Confirm the DHW and heating circuit pumps are field supplied and correctly sized.
Applies to: Vitocrossal 300 CA3B Dual Fuel with DHW tank and two heating circuits
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Viessmann Vitocrossal 300 CA3B Dual Fuel installation manual, p. 46. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.