Slab curing function (mixing valve circuit)

Vitotronic 200

What is going on

Slab curing is available only with a heating circuit that has a mixing valve. Four temperature and time curves are selected with coding F1. While active, the mixing valve circuit pump runs and the supply temperature follows the chosen curve. After 30 days the mixing valve circuit returns to its normal preset parameters. The function is kept after a power failure. Ending the function or manually resetting F1 to 0 starts the normal heating program.

Check in this order

  1. Only use slab curing on a heating circuit with a mixing valve.
  2. Select curve 1 to 4 with coding F1, or set F1:0 to turn it off.
  3. Check the curve values on the printed graph; the numbers are not legible in the text extract.

Applies to: Heating circuit with mixing valve, coding F1

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 200 KW2 service instructions, p. 52. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.