Gas line sizing and installation requirements before connecting the boiler to the gas supply.
Check in this order
- Size the gas pipe per CAN/CSA B149.1 and .2 or ANSI Z223.1/NFPA 54 and local codes, using pipe length, fittings, gas type and total input of all appliances.
- Make sure there is no noticeable pressure drop when this unit or any other unit lights or runs.
- Lay out the piping so it does not block serviceable components.
- Install a ground joint union, a capped drip leg and a manual equipment shutoff valve. Use valves listed by a nationally recognized testing agency.
- Identify the shutoff valves with a tab and show the operator where they are.
- On LPG installations in rooms below ground level, install an external safety solenoid valve.
Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352 on natural gas or LPG
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Installation Instructions, p. 19. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.