Viessmann · Boiler troubleshooting

Slab curing (screed drying) function

Vitotronic 100 GC1Vitocontrol-S VD2/CT3/CM2

What is going on

Used to dry a new concrete floor slab with a controlled supply temperature profile. Set F1 to 1 to 4 for profile 1 to 4. Profiles run over 30 days with supply temperatures up to about 50 °C.

Check in this order

  1. Set coding F1 to the required profile (1 to 4).
  2. Follow the slab curing supplier's instructions and local regulations.
  3. Record heat-up data with the supply temperatures, the maximum supply temperature reached, and the operating condition and outdoor temperature at handover.
  4. Expect the function to continue after power failure or after the control unit is switched off.
  5. Heating program restarts after screed drying finishes, or if the address is set manually to 0.

Applies to: Mixing valve circuit, screed drying

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocontrol-S, VD2/CT3/CM2 Installation and Service Instructions, p. 180 and 183. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.