Two space heating zones using zone valves (no DHW)
What is going on
Input 1 runs the system circulator. Zone valve systems need a bypass pressure regulating valve because flow can occur with the valves closed.
Check in this order
- Install a bypass pressure regulating valve. Flow can occur with zone valves closed.
- Wire space heating thermostats to Inputs 2 and 3, keeping them on Priority 2.
- Set Priority 2 for the heating system type and confirm RUN AUX PUMP/OUT is YES.
- Assign Input 1 to AUX PUMP/OUTPUT and choose ANY INPUT BY ITS PRIORITY so the system pump runs on any zone call.
- Do not wire a thermostat to P11-4/5 because Input 1 is used for the system circulator.
Applies to: SVF Series 1 with zone valves
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 1500-3000 Series 1 boiler manual, p. 67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.