Weil-McLain · Boiler troubleshooting

Two space heating zones using zone valves (no DHW)

SVF Series 1

What is going on

Input 1 runs the system circulator. Zone valve systems need a bypass pressure regulating valve because flow can occur with the valves closed.

Check in this order

  1. Install a bypass pressure regulating valve. Flow can occur with zone valves closed.
  2. Wire space heating thermostats to Inputs 2 and 3, keeping them on Priority 2.
  3. Set Priority 2 for the heating system type and confirm RUN AUX PUMP/OUT is YES.
  4. Assign Input 1 to AUX PUMP/OUTPUT and choose ANY INPUT BY ITS PRIORITY so the system pump runs on any zone call.
  5. Do not wire a thermostat to P11-4/5 because Input 1 is used for the system circulator.

Applies to: SVF Series 1 with zone valves

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF 1500-3000 Series 1 boiler manual, p. 67. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.