Weil-McLain · Boiler troubleshooting

Multiple boiler vent/air terminations

Ultra Series 4

What is going on

Several Ultra boilers on one roof or wall need matched terminations and minimum spacing. Wrong heights or spacing can cause severe injury, death or property damage.

Check in this order

  1. Terminate all vent pipes at the same height and all air pipes at the same height.
  2. Place roof penetrations for at least 12 in between the edge of an air intake elbow and the adjacent boiler's vent pipe (US installations; see Figure 23).
  3. In Canada, meet the clearances in CAN/CSA B149.1 or B149.2.
  4. Treat the Ultra air inlet as part of a direct vent connection, not as a forced air intake, for spacing from adjacent boiler vents.

Applies to: Multiple Ultra boilers sharing roof or wall terminations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Weil-McLain Ultra Series 4 boiler manual, p. 24. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.