Weil-McLain · Boiler troubleshooting

Separate low water cut-off installation

ECO Tec Series 3

What is going on

A separate low water cut-off is required and must be supplied by the installer, even though the control has inherent protection. The LWCO mounts on an added tee between the top pipe and the pressure sensor, using a 3/4 in female NPT port. Electrode probe type is recommended and must be designed for water.

Check in this order

  1. Install an additional tee between the top pipe and the pressure sensor.
  2. Mount the LWCO in the 3/4 in female NPT port location.
  3. Use a LWCO designed for water installations, electrode probe type recommended.
  4. If using the Weil-McLain LWCO kit, bundle extra wire with zip ties and keep it away from internal components.
  5. Wire the LWCO per the field wiring section.

Applies to: All ECO Tec Series 3 boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec Series 3 Boiler Manual, p. 47. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.