Separate low water cut-off installation
What is going on
A separate low water cut-off is required and must be supplied by the installer, even though the control has inherent protection. The LWCO mounts on an added tee between the top pipe and the pressure sensor, using a 3/4 in female NPT port. Electrode probe type is recommended and must be designed for water.
Check in this order
- Install an additional tee between the top pipe and the pressure sensor.
- Mount the LWCO in the 3/4 in female NPT port location.
- Use a LWCO designed for water installations, electrode probe type recommended.
- If using the Weil-McLain LWCO kit, bundle extra wire with zip ties and keep it away from internal components.
- Wire the LWCO per the field wiring section.
Applies to: All ECO Tec Series 3 boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: ECO Tec Series 3 Boiler Manual, p. 47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.