Weil-McLain · Boiler troubleshooting
Vent and air piping installation (general run rules)
What is going on
General rules for running vent and air pipe from the boiler to the termination.
Check in this order
- Use only the vent materials and kits listed in the venting materials table (Table 9, page 33).
- Use a locking collar on every joint of polypropylene vent piping; missing collars can leak.
- Use sweep elbows only. Do not use short-radius elbows in vent or air piping.
- Install a vent adapter or reducer where needed, following the vent maker's instructions.
- Slope vent piping back toward the boiler at least 1/4 in per foot on horizontal runs, or more if the vent maker requires.
- Support the piping independently of the boiler, with supports at least every 5 ft on horizontal and vertical runs, and a hanger within 6 in of any upturn.
- Brace individual external vent and air pipes no more than 24 in apart. Keep the total length of each external pipe to 4 ft or less unless it is enclosed.
- If an external vent or air pipe is longer than 4 ft, put it in an insulated enclosure to reduce condensate freezing inside the pipe, and pass the terminations through that enclosure while keeping required clearances.
- Seal exterior openings thoroughly with exterior caulk.
Applies to: SVF direct vent piping, all termination types
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SVF 500/600 Series 1 Boiler Manual, p. 51. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.