Remote modulation via 0-10 VDC on Input 2
What is going on
Input 2 can be used for remote modulation on single boilers only. Networks cannot use 0-10 V remote modulation. The priority assigned to Input 2 cannot be used by any other input.
Check in this order
- Go to Contractor Menu, System Settings, then select the priority.
- Select Input 2 and change its source to 0-10V.
- Confirm the priority assigned to Input 2 is not used by another input.
Applies to: Single boilers
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Series 2 Advanced Manual, p. 11. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.