Weil-McLain · Boiler troubleshooting

Check ignition system safety shutoff device

ECO Tec Series 3

What is going on

Confirm the ignition safety device locks out when there is no fuel.

Likely causes

  • No gas reaches the burner during the test (manual gas valve closed)

Check in this order

  1. Turn off the boiler.
  2. Close the manual gas valve on the gas line.
  3. Turn the boiler on. It will attempt ignition but will not light, then lock out and show Ignition Fault 1.
  4. Clear the lockout by selecting Manual Reset on the Homeowner screen menu.
  5. Open the manual gas valve to restore fuel supply.

Applies to: ECO Tec Series 3 gas boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: ECO Tec series 3 boiler manual, p. 136. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.