What is going on

The SVF 1500 to 3000 can run as Category II (negative pressure, likely to condense) in addition to Category IV. Category II needs an engineered vent system designed by a professional and vertical termination only.

Likely causes

  • Positive pressure in a Category II vent system causes flue gas spillage and CO emissions

Check in this order

  1. Have a professional design the vent system to local authority requirements.
  2. Use vertical vent termination only.
  3. Do not connect to an existing common vent with other appliances.
  4. Supply combustion air from the boiler room with direct exhaust openings, see page 33.
  5. Install 3 ft of straight 8-inch or 10-inch pipe directly after the vent adapter, before any diameter or direction change.
  6. Keep negative pressure at the boiler outlet within the Table 2 range during all firing rates.
  7. Keep flue gas temperature at or below 210 deg F. The boiler shuts down and recycles above 210 deg F and starts to reduce firing rate at 200 deg F.
  8. Expect flue gas temperature about 20 to 30 deg F above return water temperature. Use the lowest expected return temperature for calculations.
  9. Install a CO detector in the boiler room on the same electrical circuit as the boiler, and check local code for more requirements.

Applies to: SVF 1500, 2000, 2500, 3000 in Category II

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SVF Series 1 Boiler Manual, p. 29. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.