Check static and running gas supply pressure
What is going on
Measure at the inlet test nipple on the gas combination valve. All readings are taken under high fire.
Check in this order
- Take a CO2 measurement before and after working on the gas appliance.
- Make sure there is no open flame in the room.
- Remove the burner cover panel as described for the front panel removal.
- Close the gas shut-off valve.
- Loosen the screw in test nipple A without removing it. Connect a calibrated manometer.
- Open the gas shut-off valve and measure static pressure. Max is 14 in w.c. for natural gas and LPG.
- Start the boiler with the service switch and measure the running pressure under high fire.
- Use an instrument with at least 0.04 in w.c. resolution for running pressure.
- Record the gas pressure and gas type in the Maintenance Record on page 99.
- Switch off the boiler, close the gas shut-off valve, remove the manometer and retighten test nipple A.
- Open the gas shut-off valve and check the test nipple and all gas connections for leaks.
- Test for leaks with soap and water only. Never use matches, candles, flame or ignition sources, and never purge gas into the combustion chamber.
Applies to: Natural gas and LPG supply
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitodens 100-W, B1HE/B1KE Combi Installation/Service instructions, p. 47. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.