Viessmann · Boiler troubleshooting
Condensate disposal and neutralization
What is going on
Condensate from the boiler is acidic. Neutralize it before disposal if local rules require it.
Likely causes
- Condensate pH is about 3 to 4 (boiler) and within the 3 to 5.5 range given for the venting connection
Check in this order
- Check local building requirements for condensate disposal.
- If neutralizing is required, use a neutralization tank sized by Viessmann.
- Confirm treated condensate reads pH 6.5 to 9 before it goes to the drain.
- Condensate from the chimney can be collected with boiler condensate and sent to a floor drain.
Applies to: Vitocrossal 300 CA3B, all sizes 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Operating Instructions, p. 10. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.