Weil-McLain · Boiler troubleshooting
Locate the sidewall vent/air termination
What is going on
Pick a location that keeps flue products, condensate and wind effects away from people, plants, windows and building surfaces.
Check in this order
- Do not terminate next to a wall or under eaves, parapets, balconies or decks.
- Keep vapors away from shrubs, plants and air conditioning equipment.
- Avoid spots where the plume will block window views, where prevailing wind can freeze condensate, or where flue products can hit people or pets.
- Avoid inside building corners, areas near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards and other recessed areas where wind can cause recirculation.
- Do not terminate above a door or window or under a deck.
- Locate or guard the vent so condensate does not damage exterior finishes.
- Place terminations where foreign objects, leaves or sediment are unlikely to build up or damage them.
- For multiple Ultra boilers, terminate every vent and air inlet at the same height.
- The air inlet is part of a direct vent connection and is not treated as a forced air intake for spacing from adjacent boiler vents.
- Combustion air (not vent piping) may be manifolded per Figure 59 on page 59.
- Maintain the clearances in the Termination clearances setting.
Applies to: Ultra boilers with Weil-McLain sidewall vent/air cap or separate sidewall terminations
More boiler guides
- 0-10 VDC output for controlling another heat source (P16 pins 1 and 2)
- 0-10 VDC remote modulation input
- 0-10VDC output for lead/lag and variable speed pump
- 120 VAC power supply connection to terminal strip T1
- A sensor is missing from the list at power-up
- Access and clean exchanger, Ultra-155, -230, -299 and -399
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Ultra Series 4 boiler manual, p. 68-69. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.