Weil-McLain · Boiler troubleshooting

Locate the sidewall vent/air termination

Ultra Series 4

What is going on

Pick a location that keeps flue products, condensate and wind effects away from people, plants, windows and building surfaces.

Check in this order

  1. Do not terminate next to a wall or under eaves, parapets, balconies or decks.
  2. Keep vapors away from shrubs, plants and air conditioning equipment.
  3. Avoid spots where the plume will block window views, where prevailing wind can freeze condensate, or where flue products can hit people or pets.
  4. Avoid inside building corners, areas near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards and other recessed areas where wind can cause recirculation.
  5. Do not terminate above a door or window or under a deck.
  6. Locate or guard the vent so condensate does not damage exterior finishes.
  7. Place terminations where foreign objects, leaves or sediment are unlikely to build up or damage them.
  8. For multiple Ultra boilers, terminate every vent and air inlet at the same height.
  9. The air inlet is part of a direct vent connection and is not treated as a forced air intake for spacing from adjacent boiler vents.
  10. Combustion air (not vent piping) may be manifolded per Figure 59 on page 59.
  11. Maintain the clearances in the Termination clearances setting.

Applies to: Ultra boilers with Weil-McLain sidewall vent/air cap or separate sidewall terminations

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Ultra Series 4 boiler manual, p. 68-69. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.