Viessmann · Boiler troubleshooting
Set CO2 at upper heating output
What is going on
Adjust CO2 at full load. Only the burner being adjusted may run; the other burners must be at standstill.
Check in this order
- Open the gas shut-off valve.
- Start the burner with the emissions test switch enabled at the control unit.
- Press the button until the service display shows 100 (100%).
- Read the CO2 level at the flue pipe.
- If CO2 is out of range, remove cap B.
- Turn adjusting screw A in small steps with a 3 mm Allen key. Clockwise lowers CO2 (less gas). Counter-clockwise raises CO2 (more gas).
- Record the value in the maintenance report on page 162.
Applies to: CA3B 2.5 to 6.0
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B Series 2.5 to 6.0 Service Instructions, p. 67. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.