Viessmann · Boiler troubleshooting
Burner does not start or starts intermittently (red fault LED flashing)
What is going on
Burner fault LED flashes and the burner starts and stops.
Likely causes
- Burner is not electrically connected.
- Fixed high limit (FHL) has tripped.
Check in this order
- Confirm the 7-pole plug-in connection to the burner and power venter is made.
- Reset the FHL by pressing in the pin labelled E with a ballpoint pen.
- If a click is heard, the limit had tripped; find and correct the cause before restarting.
Applies to: Vitotronic 100 KW10B with burner
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitotronic 100 KW10B installation, start-up and service instructions, p. 27. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.