Viessmann · Boiler troubleshooting

Burner does not start or starts intermittently (red fault LED flashing)

Vitotronic 100

What is going on

Burner fault LED flashes and the burner starts and stops.

Likely causes

  • Burner is not electrically connected.
  • Fixed high limit (FHL) has tripped.

Check in this order

  1. Confirm the 7-pole plug-in connection to the burner and power venter is made.
  2. Reset the FHL by pressing in the pin labelled E with a ballpoint pen.
  3. If a click is heard, the limit had tripped; find and correct the cause before restarting.

Applies to: Vitotronic 100 KW10B with burner

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitotronic 100 KW10B installation, start-up and service instructions, p. 27. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.