Viessmann · Boiler troubleshooting
Setting the operating program
What is going on
Choose the operating program for a heating circuit from the menu.
Check in this order
- From the home screen tap Menu, Heating, the required heating circuit, then Operating program.
- Select the program, for example Heating and DHW.
- Press OK to confirm.
Applies to: Vitocrossal 300 CA3B
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 300 CA3B operating instructions, p. 22. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.