Assembling the boiler base

Vitorond 200 VD2A

What is going on

Steps to set up the base and crossbar before fitting the cast iron sections.

Check in this order

  1. Install the levelling bolts and set them to their lowest position.
  2. Level the boiler base with the levelling bolts.
  3. Screw in the bolts or anti-vibration bolts. Levelling foot B is only used on sizes 230 and 270.
  4. Install crossbar A with its larger cut-out facing the front of the boiler.
  5. Use a level to confirm the base is level.
  6. Support the cast iron sections with field-supplied support A before assembly to prevent tipping.
  7. Place the cast iron leg section firmly on the base and shim if needed.
  8. Cross bar larger cut-out moves to its end during cast assembly.
  9. After assembling the cast iron sections, re-level the boiler with the levelling bolts.

Applies to: Vitorond 200 VD2A

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitorond 200 VD2A installation instructions, pp. 13-15. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.