Weil-McLain · Boiler troubleshooting

Additional limits and low water protection

SlimFit Series 3 Commercial

What is going on

The control provides high limit and low water protection. Some jurisdictions require external limits.

Check in this order

  1. Check local codes to see if extra limit devices are needed.
  2. For low temperature circuits on a mixed system, wire external limits to the control P13 terminals.
  3. For manual reset, use series isolated contacts on P13 terminals 1 and 2.
  4. For automatic reset, use series isolated contacts on P13 terminals 3 and 4.
  5. Test the push-to-test low water cutoff on the supply manifold by removing the jacket. It resets manually through the control.
  6. Install a backflow check valve in the cold water supply where local codes require it.

Applies to: All SlimFit boilers

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: SlimFit 550/750 Series 3 boiler manual, p. 12. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.