Additional limits and low water protection
What is going on
The control provides high limit and low water protection. Some jurisdictions require external limits.
Check in this order
- Check local codes to see if extra limit devices are needed.
- For low temperature circuits on a mixed system, wire external limits to the control P13 terminals.
- For manual reset, use series isolated contacts on P13 terminals 1 and 2.
- For automatic reset, use series isolated contacts on P13 terminals 3 and 4.
- Test the push-to-test low water cutoff on the supply manifold by removing the jacket. It resets manually through the control.
- Install a backflow check valve in the cold water supply where local codes require it.
Applies to: All SlimFit boilers
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: SlimFit 550/750 Series 3 boiler manual, p. 12. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.