Viessmann · Boiler troubleshooting
Burner harness and cable strap routing
What is going on
Secure the burner harness to the side panel with the supplied cable straps. Leave no slack so the burner door can swing open without unplugging the harness.
Check in this order
- Secure the control harness with the two supplied cable straps.
- Coil the extra harness on the side panel with no slack.
- For Beckett or Carlin burners, cut the harness length to 6 in. for the burner junction box under the primary control.
- For Riello burners, leave the harness at full length (marked as Riello only).
- Do not run conduit through the cover mounting plate. Pass it through the front opening or a side knockout into the 4x4 burner junction box.
Applies to: Burner wiring harness on VR1 boilers
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitorond 100 VR1 installation and service manual, p. 29 and p. 30. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.