Gas pressure switch 2 fault shutdown (leak test of safety valves)

Vitocrossal 200 CI2

What is going on

Gas pressure switch 2 (red, VPS pressure) checks the gas safety valves for leakage each time the burner starts. Excessive leakage causes a fault shutdown.

Likely causes

  • Leakage through the gas safety valves
  • Faulty gas pressure switch 2

Check in this order

  1. Reset the burner control unit from the control unit and restart the burner.
  2. If fault 885 or 887 repeats, replace the gas solenoid valve.

Applies to: 750/1000 MBH burner (gas pressure switch 2)

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitocrossal 200 CI2 service instructions, p. 92. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.