Gas pressure switch 2 fault shutdown (leak test of safety valves)
What is going on
Gas pressure switch 2 (red, VPS pressure) checks the gas safety valves for leakage each time the burner starts. Excessive leakage causes a fault shutdown.
Likely causes
- Leakage through the gas safety valves
- Faulty gas pressure switch 2
Check in this order
- Reset the burner control unit from the control unit and restart the burner.
- If fault 885 or 887 repeats, replace the gas solenoid valve.
Applies to: 750/1000 MBH burner (gas pressure switch 2)
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Vitocrossal 200 CI2 service instructions, p. 92. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.