Viessmann · Boiler troubleshooting

Service display: acknowledge and reset

Vitodens 200-W B2HA

What is going on

When the hours or time limits in coding 21 and 23 are reached, the red fault indicator flashes and the programming unit shows the Service message. Acknowledging it does not reset it.

Likely causes

  • Burner hours run limit (coding 21) reached
  • Service time interval (coding 23) reached

Check in this order

  1. Press OK to acknowledge the service message.
  2. Note that an acknowledged message that was not reset returns on the following Monday.
  3. After the service is done, press OK and the second button shown in the manual together for about 4 seconds.
  4. Select Service functions, then Service reset.
  5. Check that the hours and interval counters restart at 0.

Applies to: Vitodens 200-W B2HA 80-100

More boiler guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Vitodens 200-W B2HA service instructions, p. 41. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.