Weil-McLain · Boiler troubleshooting
Replace burner orifices
What is going on
Use this when the orifice size must be changed. Follow with the final check-out.
Check in this order
- Remove the burner shield screws and take off the shield.
- Use a 7/16 inch open-end wrench to remove the burner orifices from the manifold.
- Put a small amount of propane-compatible pipe dope on each new orifice.
- Install the new orifices with the 7/16 inch wrench. Check they are aligned and not cross-threaded.
- Reinstall the burner shield.
- Run the final verification checklist (page 66) to confirm proper operation.
Applies to: CGi-25 to CGi-8
More boiler guides
Related
Weil-McLain error codes · Weil-McLain parts · Weil-McLain tips · Calculators and reference tables
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: CGi Series 5 Gas-Fired Water Boiler boiler manual, p. 16. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.