Rinnai · Boiler troubleshooting
Radiators not hot enough or slow to heat
What is going on
Heating performance is poor.
Likely causes
- Room thermostat or RS100 setting
- Supply temperature setpoint too low
- Wrong installation type in parameter 2
- System resistance too high (boiler cuts load when delta T exceeds 36 F)
Check in this order
- Check thermostat / RS100 settings.
- Check PARA parameter 1 and raise if needed.
- Check PARA parameter 2.
- Check and clean the water filter; verify pipe sizing.
Applies to: E50CRN; E75CRN; E75CRP; E110CRN; E110CRP
More boiler guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: Rinnai E-Combi Series Installation & Servicing Instructions (8U516009 V0116), p.77 (15.4). Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.